Skip to content
STEEL CABLE & WIRE ROPE INSTRUMENTS Application-led selection · Global B2B inquiries
CTMRIGGING & FORCE INSTRUMENTS
Menu
Home / Cable sensor interfaces

FOR PLC INTEGRATORS / CONTINUOUS ROPE MONITORING

Cable tension sensors. Match the PLC signal.

Check signal scaling, then define the rope sensor and controller interface together.

Published and reviewed November 1, 2026 · CTM Engineering

Scale a PLC signal to cable tension

Example defaults: 12 mA and a declared 0–200 kN scale. Replace with the transmitter's confirmed endpoints.

Changing the signal clears its reading; changing force units clears the endpoints. Enter the confirmed values in the new units. Reverse/nonlinear scales, raw PLC counts and protocol decoding are outside this tool.

Add cable and installation details for the RFQ
100 kNFixed software example · 50% of signal span

Linear scaling only. This does not verify rope calibration, measured accuracy, wiring or a safe working load.

An in-span signal can still represent the wrong rope profile or mechanical setup. Use the report below to separate scaling, calibration and commissioning.

Request PLC interface review ↗

Keep rope calibration and electrical scaling separate.

A cable tension sensor turns a defined mechanical input into an electrical signal. The PLC then interprets that signal. An accurate arithmetic conversion can still display the wrong force if the rope profile, installed geometry or transmitter configuration is wrong.

Agree three identities: the actual rope and contact arrangement, the delivered sensor/conditioner, and the receiver's configured scale. Keep their records together rather than correcting an unexplained error with a display offset.

Review CTM-FIX clamp and calibrated-range requests →
Conceptual measurement chain from rope and clamp through signal conditioner to PLC scale, with separate mechanical and electrical checks
Original concept diagram. Block order describes review responsibilities, not terminal wiring or a released CTM installation.

Start with the output actually supplied at the sensor cable.

The same mechanical sensing task can use different electronics. Match the delivered output to the input module before comparing a bare sensor price with a complete channel.

Output pathReceiver to specifyEvidence needed before connection
Raw mV/V bridgeMatched strain-gauge input or conditioner with specified excitationBridge sensitivity, excitation, cable/sense arrangement and conditioner calibration; do not treat this as a 0–10 V transmitter.
Conditioned 4–20 mACompatible current input and correctly powered loopActive/passive roles, two-/three-/four-wire topology, supply/load limits and force endpoints.
Conditioned 0–10 VCompatible voltage input with the specified referenceSupply, common/reference connection, input impedance, isolation and scaled endpoints.
RS485 digitalCompatible physical port plus the actual protocol implementationProtocol, device address, serial settings, register/data definition, units and timeout/status behavior.
Wireless sensor and receiverNamed receiver/gateway with the required onward outputThe wireless link and PLC connection are separate selections; request the complete receiver-to-controller specification.

Source scope: SENSY 5560S, PDF page 4, shows configuration-dependent electrical options; individual control sheet governs.

A stationary clamp and a moving-line sensor solve different problems.

The electrical interface does not decide how the sensor may contact the rope. Keep the operating mode and load path explicit in the request.

Measurement taskArrangement to reviewWhat cannot be inferred
Continuous readings on a stationary cable sectionCTM-FIX bolted clamp request with matched geometry and rope profileA family diameter envelope does not approve every rope or usable low-load range.
Cable moving through the measuring assemblyCTM-RLT running-line request with sheaves, bend limits and speed scopeA fixed clamp is not a running guide; an analog output does not make it suitable for moving rope.
Portable readings on an accessible stationary spanCTM-QC meter request; agree logging or optional interface separatelyA local display or Bluetooth report is not automatically a continuous PLC channel.
An in-line device or changed load path is proposedSeparate mechanical-system and installation reviewThe CTM clamp-on catalog does not establish an approved in-line component or an interchangeable load path.

Source scope: SENSY 5560S fixed-cable scope, PDF page 2; CTM family references remain planning requests.

Permanent rope clamp sensor with two grooved saddles, bolt bridge and blue cable
Supplier reference photographs. Exact model, rope fit, calibration and supplied accessories are agreed in the written offer.

Read the output specification before choosing the PLC module.

A cable emerging from a clamp does not identify its output type. Ask for the supplied option code, terminal drawing, excitation/supply range and individual control sheet. The historical SENSY 5560S manual, page 4, demonstrates why the configuration matters.

For a CTM-FIX request, provide the input module and required output along with the rope. A quoted conditioned signal, raw bridge, remote receiver and relay controller are different line items.

Request the complete sensor-to-PLC scope →

Specify the controller and terminal arrangement separately.

A controller enclosure is not a signal specification. Confirm the exact part number, supply, receiver, wiring drawing and protocol for the delivered configuration.

White DIN-rail control enclosure with blue cover, six keys and terminal openings
DIN-rail control unitControl enclosure, keys and terminal openings. The pictured source label differs from its listing; confirm exact part number and wiring.
Gray rope-load controller with red display, seven keys and three lower cable fittings
Rope-load controller enclosureDisplay, seven keys and lower cable fittings. Connector appearance does not establish protocol, relay function or compatibility.

Supplier reference photographs. Exact model, rope fit, calibration and supplied accessories are agreed in the written offer.

Two endpoints define the linear signal-to-force map.

The worksheet uses F = F_low + (S − S_low) × (F_high − F_low) / (S_high − S_low). For 4–20 mA, S_low = 4 and S_high = 20. For 0–10 V they are 0 and 10. Force units must match both entered endpoints.

This is interpolation of a declared increasing linear scale. The actual transmitter characteristic must be confirmed before applying it. Rockwell's scaling explanation describes translating configured signal endpoints into engineering values. The worksheet rejects a reversed/zero force span and suppresses force outside the signal span instead of extrapolating.

Software input bound: absolute values up to 1,000,000,000. This is a numerical worksheet limit, not a CTM instrument range. Results are displayed to six decimal places; downloads preserve the original typed inputs and the calculated number. No physical accuracy is implied by the number of displayed digits.

Enter current in mA, not A. Confirm the actual signal endpoints even when a product name says “voltage output”: a 1–5 V or other offset signal cannot use this worksheet's exact 0–10 V mode. Use the supplied control sheet and a calculation matching those actual endpoints.

Compare the sensor, receiver and controller as one quoted channel.

Primary-source examples reviewed November 1, 2026. These are architecture differences, not drop-in cross-references, price comparisons or current availability promises.

Named referencePublished architectureQuestion for the written offer
SENSY 5560SFixed-cable sensor; its 2017 manual lists several electrical variants and refers to the individual control sheet.Which exact output/option, control sheet, matched rope and terminal drawing are supplied?
Straightpoint BOLTKito Crosby identifies proprietary 2.4 GHz transmission to selected receivers.Which receiver and onward PLC interface are included? Do not assume a current loop from the wireless description.
Gigasense CSMA controller evaluating force-transmitter inputs and assigned system functions.Which sensors, channel definitions and system validation are included? Its declared system attributes do not apply to another sensor.
CTM-FIX requestRope-specific clamp and 4–20 mA / 0–10 V / RS485 interface requirements can be submitted.Request a released drawing, confirmed electronics, calibrated force band and commissioning record; the request is not a verified product release.

Vendor references: SENSY 5560S manual · Kito Crosby BOLT · Gigasense CSM. Read the individual configuration and document revision; no universal pinout is supplied here.

Keep out-of-span signals separate from normal tension values.

The worksheet checks a declared measuring span only. The integrator must use the actual equipment documentation for diagnostics and machine response.

ObservationInterpretation boundaryUseful next check
4 mA on a configured 4–20 mA channelCorresponds to the declared lower engineering endpoint, which need not be zero force.Compare the transmitter scale, PLC scale and reference record.
0 mA on that current channelOutside the normal measuring span; do not display it as zero cable tension.Investigate power, wiring, receiver and documented diagnostic states before interpreting load.
0 V on a 0–10 V channelCan be a legitimate lower-end signal; the number alone does not distinguish every failure.Review independent status/diagnostic provisions and the actual wiring.
Reading inside the expected spanDoes not prove correct rope geometry, profile, zero reference or calibration.Compare the installed mechanical setup and independent reference load.
Valid serial frames but implausible forceCommunication success does not establish the correct data interpretation.Check address convention, units, sign, scale, word order, freshness and status definition.

Source scope: NI current-loop fundamentals; diagnostic interpretation remains device-specific.

RS485 needs a protocol and data map before it means tension.

Analog Devices AN-960 distinguishes RS485's electrical layer from the protocol used above it. A working physical connection does not identify which bytes represent force.

Include these serial-interface questions in the offer.

  • Actual protocol and supported functions; device address, baud rate, parity and stop bits.
  • Register/address convention, data type, sign, scale factor, engineering unit and byte/word order for multi-register values.
  • Measured update rate versus PLC polling rate; timestamps or freshness indication where supplied.
  • Status/diagnostic definitions, communications timeout and required response to missing or stale data.
  • Approved terminal, shield/reference, termination, bias and isolation details for the actual equipment/network.

This is CTM's interface-review checklist, not an invented Modbus register map or wiring instruction. An RS485 request does not establish that a CTM configuration supports Modbus.

Request RS485 documentation ↗

Separate electrical injection from a rope-load acceptance test.

A repeatable commissioning record identifies what each check actually exercises. The following is a request/record framework, not an instruction to energize or load equipment.

Check layerRecordWhat it establishes / leaves open
Configuration reviewSensor, conditioner, PLC module, firmware/map, drawings and rope IDsConfirms document identity; does not measure physical performance.
Electrical scaling checkAgreed injected signal points, receiver readings and engineering displayExercises receiver/scaling logic; bypasses the rope sensor and its calibration.
Installed force-reference checkApproved load/reference method, rope profile, conditions and observed readingsTests the defined installed chain over the agreed points; scope and uncertainty must be stated.
Status and alarm responseDocumented simulated fault, delays, latch/reset and observed controller responseValidates the agreed test cases only; system acceptance remains with the responsible integrator.
HandoverAs-left settings, records, revision, responsible person and service procedureMakes future comparisons reproducible; retain the raw signal and interpreted value.
Commissioning review separates document identity, electrical injection, installed rope reference and documented status response
Original acceptance-record framework. Electrical injection and an installed rope-reference check exercise different parts of the chain.

Three software scenarios expose different integration questions.

Illustrative arithmetic only, using the stated inputs. These are not sensor measurements, calibration results or customer cases.

12 mA → 100 kN

Given 4–20 mA mapped to 0–200 kN, the midpoint produces 100 kN and 50% of span. A matching PLC display checks scaling arithmetic; it does not confirm the rope profile.

2.5 V → 35 lbf

Given 0–10 V mapped to 10–110 lbf, 25% of signal span produces 35 lbf. A nonzero lower force must be retained rather than silently replaced by zero.

3.5 mA → review signal

Given the same 4–20 mA span, the tool supplies no force. Confirm the signal/receiver and documented diagnostic state; no negative force, zero clamp or automatic alarm command is inferred.

Try the declared signal and endpoints →
Actual software example scaling 12.34567 mA on a declared 0 to 237.12345 kN linear range
Actual software capture, November 1, 2026. Inputs: 4–20 mA, 12.34567 mA, lower endpoint 0 kN and upper endpoint 237.12345 kN. This demonstrates the arithmetic and review handoff, not a sensor reading, calibration record or customer result. Reproduce the software example →

Specify the documents and inclusions before comparing channel cost.

A low bare-sensor quote can omit the components or records that make a channel usable. Use this checklist for a like-for-like RFQ.

Quotation lineState in your requestConfirm in the response
Mechanical and rope scopeDiameter, construction/material, normal/peak force, stationary/moving condition and clearanceExact clamp/contact drawing, rope profile, usable force band and installation procedure.
Electronics and cableRequired output, PLC module, supply, run length and environmental conditionsSensor/conditioner/receiver inclusion, terminal assignment, limits, cable/connector scope and protection evidence.
Calibration and recordsActual rope-profile list, force band, error definition and required documentationProfile identity, load points, reference, results, uncertainty and acceptance criteria.
Commissioning and lifecycleRequired status behavior, logging, service access, quantity and destinationTest plan, documentation, recalibration/support terms and actual commercial delivery scope.

Send the interface assumptions with the rope request.

The worksheet carries the chosen signal, exact typed endpoints and reading, rope identity and multiline notes into the shared RFQ. Add the required quantity, destination and actual project schedule there. You can also list up to 15 requested rope profiles for engineering review.

Build the PLC interface request ↗

List individual rope-profile requirements →

Cable sensor output and commissioning questions

Is a cable tension sensor the same as a handheld meter?

A sensor supplies a signal to a receiver or controller; a handheld meter is normally used for local checks. Some products combine functions, so identify the required operating mode, output and recording path in the offer.

Can a raw mV/V sensor connect to a normal voltage input?

Do not assume it can. Specify the bridge excitation and sensitivity and use a matched bridge input or conditioner. A raw bridge signal and a conditioned 0–10 V signal require different receiver arrangements.

Does 4 mA always mean zero cable tension?

No. It represents the lower endpoint assigned to that linear scale. If the confirmed lower force is 10 kN, the matching 4 mA display value is 10 kN. The worksheet lets you enter a nonzero lower endpoint.

Does the calculator create a rope calibration curve?

No. It interpolates between two declared electrical/engineering endpoints. It does not determine cable stiffness, contact deflection, calibrated accuracy, an approved rope profile or the physical load on your cable.

Why is there no force result below 4 mA?

This worksheet deliberately stops outside its declared measuring span. It does not extrapolate or replace a suspect value with zero. Follow the actual device diagnostic documentation before interpreting load.

Can zero volts be treated as a broken wire?

Not from the signal number alone on a 0–10 V scale. Zero volts may be a valid lower-end value. Agree separate status and fault-detection behavior for the actual equipment and installation.

Does an RS485 label guarantee Modbus RTU?

No. RS485 identifies an electrical interface. Request the actual protocol, serial settings and data map. If Modbus is offered, obtain its supported functions, addressing convention, data format, units and status behavior.

Can the tool convert PLC raw counts?

No. Enter a measured/configured current in mA or voltage in V. Raw-count endpoints and diagnostics depend on the input module and its selected range; use the module documentation before converting those counts.

Does BOLT wireless communication provide the PLC output I need?

The primary BOLT page describes selected wireless receivers. Specify the required onward controller interface and ask for the exact receiver/gateway configuration. A wireless link alone does not establish a direct 4–20 mA connection.

Does a correct displayed force prove overload protection?

No. A scaling calculation is one small part of a measurement chain. Mechanical limits, fault detection, control logic and the required system acceptance are separate matters for the responsible machine integrator.

Can I use the historical SENSY manual as CTM wiring instructions?

No. It illustrates how a named sensor can have configuration-dependent outputs. Use the released terminal drawing and individual control sheet for the actual supplied equipment; no SENSY wiring or ratings are transferred to CTM.

What should I send for a CTM-FIX interface quote?

Send exact rope identity and force needs, stationary mounting/access, requested signal, PLC module, supply, cable run, environment, status/alarm expectations, quantity and country. The worksheet preserves its typed inputs in the RFQ and text download.

Primary-source scope and the documents still needed

Sources reviewed November 1, 2026. Manufacturer documents govern their identified model/revision. CTM configuration-specific drawings, calibration results, electrical limits and acceptance records must be supplied with the actual offer.